Permit: T06CM04548

Parcel: 125111390


Addresses:

3617 E 3RD ST


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM04548

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
02/23/2007 FRAMING Approved IVRS - Inspection :*
02/21/2007 FRAMING Partial Approval IVRS - Inspection :*
1) RANGE HOME RUN CUT
2) FIREBLOCK DROP CEILINGS 2ND FLOOR
3) APPROVED TO INSULATE
02/12/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE WATER TEST DWV SYSTEM OR POTABLE WATER
2) BLOCK MECHANICAL PLENIUM
3) FIRESTOP ELECTRICAL PENETRATION TO UPSTAIRS
4) SECURE ALL ROMEX 8" FROM BOXES
5) ? HOME RUNS
6) NAIL PROTECT ELECTRIC THRU-OUT
7) RELOCATE 220 WIRE UPSTAIRS
8) FIREBLOCK MISSING UPSTAIRS LAUNDRY
9) SECURE 90 VENTS THRU ROOF TOP
10) NAIL PROTECT PEX THRU-OUT
11) REPAIR OVER KNOTCH UPSTAIRS INTERIOR SHEARWALL
12) FIREBLOCK UPSTAIRS MECH DROP
13) REPAIR ALL DAMAGED FIREBLOCK
14) SMOKIES MUST BE MINIMUM 36" FROM REGISTERS
15) SECURE 4 GANG BOXES BOTH ENDS