Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. UNIT #2 NEED RANGE PULLED OUT SO I CAN CHECK WIRING 2. THIS RANGE IS 14.4 KW AND REQUIRES LARGER CKT THAN WHAT YOU HAVE INSTALLED. 3. KITCHEN COUNTER RECEPTACLE NOT WORKING? HOW WAS NEW RECEPTACLE ADDED/WIRED? ROOF & UNIT #1 OK A RANGE WILL BE REQUIRED FOR A FINAL YOU WILL ALSO NEED TO PAY A REINSPECTION FEE BEFORE A FINAL APPROVAL |
|
| 04/25/2007 | ELECTRIC - FINAL | Approved | PER BLD FINAL | |
| 04/24/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* UNIT #2 -- 1. NEED RANGE 2. KITCHEN RECEPTACLE MISSING COVER 3. ROMEX SHEATHING TO EXTEND MIN. 1/4" INTO WATER HEATER DISCONNECT. 4. MAX 24" TO KITCHEN COUNTER RECEPTACLE NEXT TO RANGE FROM EDGE OF COUNTER. ON ROOF: 1. USE PROPER SIZE STRAPS TO STRAP 1/2" FLEX NOT 1" EMT STRAPS 2. SEAL OLD OPENINGS WHERE FLEX WAS REMOVED UNIT #1 1. ROMEX TO EXTEND 1/4" MIN. INTO WATER HEATER DISCONNECT BOTH UNITS -- ALL SMOKE DETECTORS TO HAVE BATTERY BACK UP POWER SOURCE. THERE WILL NEED TO BE A FEE IF ALL NOT CORRECT NEXT INSPECTION. |
|
| 04/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FOR ROOFTOP UNITS 1. WIRE SUPPLY TO K.O PROVIDED -- NOT INTO SIDE 2. IDENTIFY WHITE USED AS HOT IN DISCONNECT 3. WHERE IS THERMOSTAT WIRE? 4. SECURELY INSTALL RANGE ANTI-TIP DEVICE 5. RANGE CORD CONNECTOR NOT PROPERLY INSTALLED 6. NEED A 4 WIRE RANG -- REMOVE BOND STRAP 7. NEED ACCEPTABLE LOCK OUT DEVICE FOR WATER HEATER THIS DEVICE WILL NOT ALLOW BREAKER TO TRIP 8. REMOVE TEMP SERVICE |
|
| 01/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* UNIT 1 1. NEED LIGHT OR SWITCHED RECEPTACLE IN BEDROOMS NEC 210.70 2. HAVE DEAD RECEPTACLE EAST BEDROOM (BURIED RECEPTACLE) 3. RECEPTACLE WEST BEDROOMS SHOWS OPEN GROUND 4. PROVIDE DISCONNECTING MEANS FOR WATER HEATER - NEC 422.31B 5. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED - NEC 408.4 6. MULTI-WIRE BRANCH CKT'S NEED TO TERMINATE ON DIFFERENT PHASES IN PANEL - NEC 100 SEE MULTI-WIRE DEFINITION. 7. ROOFTOP UNITS NOT INSTALLED - EACH UNIT REQUIRES OWN SERVICE RECEPTACLE - NEC 210.63 8. EXTERIOR FLOOD LIGHTS VIOLATION OF CITY LIGHTING CODE - CHECK FOR COMPLIANCE INSPECTION FOR UNIT ONE ONLY -- CHECK FOR THESE AND OTHER PROBLEMS IN UNIT 2 |
|
| 01/29/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |