Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/01/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED - REVISE PANEL "A" DIRECTORY AND MAKE SURE ALL IS CORRECT. 2. EMERGENCY LIGHTING NOT WORKING AND NEED TO AIM LIGHTS OUT AND DOWN. 3. SINCE FIXTURE MOUNTING HAS BEEN ALTERED (SEPARATED) PROVIDE MANUFACTURER INFO ON MOUNTING METHOD. |