Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM04545
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/03/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/29/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. POT HOLES TO BE BURY 15' PLEASE UNCOVER MARKINGS AND AT LEAST ONE COUPLING CONNECTION. 2. SILICON IS COMBUSTIBLE -- NOT ALLOWED TO FILL. 3. FINISH PREVIOUS ITEMS. |
|
09/26/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. A PERMANENT MARKING ADDRESS LABEL IS NEEDED 2. LABEL BREAKERS 3. SERVICE CONDUCTORS TO BE SIZED PER 310.16 4. UNCOVER CONDUITS IN GROUND TO INSPECT TRAILERS. 1. GROUNDING ELECTRODES TO BE INSTALLED PER 250.56 2. SHEET METAL SCREWS NOT ALLOWED 250.8 3. CLEAN SURFACE UNDER GROUND BAR 250.12 4. FILL UNUSED PORTION OF OPENINGS IN PANEL 5. SECURE GROUNDING ELECTRODE CONDUCTORS WITH OTHER THAN BLACK TAPE. 6. LABEL OUTSIDE COVERS TO MATCH MAIN SERVICE. |