Permit: T06CM04539

Parcel: 10821328B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
10/16/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
10/13/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. HAVE OVERFILLED BOXES -- NEC 314.16
2. WHERE WHITE USED AS HOT, IT MUST BE REQUIRED IN
NEC 200.6, 200.7
3. EQUIPMENT GROUND FOR J-BOXES TO BE TIGHT AND HAVE NO INSULATION UNDER SCREW -- NEC 250.4 A 5