Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM04539
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/16/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/13/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. HAVE OVERFILLED BOXES -- NEC 314.16 2. WHERE WHITE USED AS HOT, IT MUST BE REQUIRED IN NEC 200.6, 200.7 3. EQUIPMENT GROUND FOR J-BOXES TO BE TIGHT AND HAVE NO INSULATION UNDER SCREW -- NEC 250.4 A 5 |