Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T06CM04533
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2007 | ELECTRIC - PROGRESS | Approved | ||
06/20/2007 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
05/30/2007 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* FOR FINAL LETTER PER OWNER 175A DISCONNECT OK |
|
05/22/2007 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The service is not per code.| 210* 1. INSTALL ADDRESS ON SERVICE 2. IDENTIFY SERVICE DISCONNECTS AS "SERVICE DISCONNECTS" AND THE PANELS THEY DISCONNECT (A, B) NEC 230.70B 3. 4/0 ALUMINUM NOT RATED FOR 200 AMP OVERCURRENT PROTECTION -- NEC 310 4. BONDING CONDUCTOR FOR DISCONNECTS & METER BASE & SERVICE RISER UNDERSIZED -- NEC 250.102 5. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT -- NEC 250.6 6. BOND METAL PIPING TO SERVICE - 250.104 7. NEED SEALING LOCKNUTS INTO METER BASE -- NEC 110 |
|
04/25/2007 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* BUILDING LOCKED REVISIONS ARE TO BE APPROVED THRU OFFICE |