Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM04532
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/06/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) OK FOR FINAL 2) AIR BALANCE OK |
|
02/05/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE AIR BALANCE REPORT |
|
01/29/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ROOF JACK REQUIRED @ ELEC. CONDUIT PAINT EXPOSED PVC BETTER PROVIDE MIN. 1/8" PER FT. SLOPE ON CONDENSATE DRAIN PROVIDE AIR BALANCE REPORT |
|
01/26/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE COVERS OVER CANVAS CONNECTORS. 2. PROVIDE FRESH AIR INTAKES. 3. DISCONNECT OVERFUSED 4. PERMANENTLY I.D UNITS & DISCONNECTS 5. PROVIDE A ROOF JACK AT ROOF PENETRATIONS 6. PROVIDE CONDENSATE DRAIN LINE 7. SECURE LOW VOLTAGE CONDUIT. |