Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/16/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* EXPOSED DUCT ON ROOF REQUIRES MIN. R8 - 2" DUCT LINER FRESH AIR, PROVIDE SPECIFICATION FOR DUCT SYSTEM AND PROVIDE NEW PERMIT FOR HP1 INSTALLATION |
|
| 04/19/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* HP1 MAY HAVE BEEN INSTALLED W/O A PERMIT EXPOSED DUCT ON ROOF REQUIRES MIN. R8 - 2" DUCT LINER FINISH INSTALL, MARK DATA PLATE, PROVIDE FRESH AIR RTU 13 - NO CONDENSATE DRAIN, DISCONNECT OVERFUSED RTU 12 - NO CONDENSATE RTU 8 - NO CONDENSATE RTU 6 - NOT COMPLETE RTU 9 - SERVICE PANEL MISSING PROVIDE PERMIT HP-1 ROOM 203 |
|
| 03/23/2007 | MECHANICAL - FINAL | Partial Approval | OK FOR TEMP C OF O, MORE COMMENTS TO FOLLOW | |
| 03/23/2007 | MECHANICAL - FINAL | Partial Approval | AC 6 INSTALL GAS LINE, CONDENSATE LINE, FRESH AIR INTAKE PROVIDE AIR BALANCE REPORT TESTED DUCT SMOKE DETECTORS OK FOR TEMP C OF O |