Permit: T06CM04531

Parcel: 140420190


Addresses:

2711 E ELVIRA RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/17/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/16/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
EXPOSED DUCT ON ROOF REQUIRES MIN. R8 - 2" DUCT LINER
FRESH AIR, PROVIDE SPECIFICATION FOR DUCT SYSTEM AND PROVIDE NEW PERMIT FOR HP1 INSTALLATION
04/19/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
HP1 MAY HAVE BEEN INSTALLED W/O A PERMIT
EXPOSED DUCT ON ROOF REQUIRES MIN. R8 - 2" DUCT LINER
FINISH INSTALL, MARK DATA PLATE, PROVIDE FRESH AIR
RTU 13 - NO CONDENSATE DRAIN, DISCONNECT OVERFUSED
RTU 12 - NO CONDENSATE
RTU 8 - NO CONDENSATE
RTU 6 - NOT COMPLETE
RTU 9 - SERVICE PANEL MISSING
PROVIDE PERMIT HP-1 ROOM 203
03/23/2007 MECHANICAL - FINAL Partial Approval OK FOR TEMP C OF O, MORE COMMENTS TO FOLLOW
03/23/2007 MECHANICAL - FINAL Partial Approval AC 6 INSTALL GAS LINE, CONDENSATE LINE, FRESH AIR INTAKE
PROVIDE AIR BALANCE REPORT
TESTED DUCT SMOKE DETECTORS
OK FOR TEMP C OF O