Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T06CM04525
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/07/2006 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* 1. APPROVED PLAN AND PERMIT ON SITE 2. OK TO COVER UNDERGROUND |
|
12/06/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. "FLAT" VENT OK! 2. DO NOT COVER! NO APPROVED PLAN ON SITE 3. CALL ALL INTERMEDIATE INSPECTIONS USING 03075 PLUMBING PROGRESS AS YOUR ENTRY CODE. |
|
12/04/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. ABS UNDERGROUND OK TO COVER WITH EXCEPTION a. LEAVE HORIZONTAL VENT BELOW GRADE OPEN FOR REINSPECTION. 1. BRIDGING NOT PERMITTED 2. BACKPITCH NOT PERMITTED 3. HORIZONTAL VENTING BELOW FLOOD RIM TO HAVE 2% PITCH. 2. POST CORRECT SUITE NUMBER ON REAR DOOR. |
|
12/02/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* |