Permit: T06CM04525

Parcel: 124041020

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/11/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/09/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROPERLY IDENTIFY ALL ROOFTOP EQUIPMENT AND USE PROPER SPACE #
2. ISLAND CONDENSER MAX FUSE 35 AMPS -- AC #14 ONE GROUND ONLY UNDER LUG
3. PANEL DIRECTORY TO BE CORRECT
4. MAX. 15 AMP FOR WALKINS PER DATA PLATES
07/02/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. WORK NOT PER PLAN, PROVIDE SEALED LETTER FROM ARCHITECT FOR DELETIONS
2. GO OVER REST OF JOB AS DISCUSSED