Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/09/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROPERLY IDENTIFY ALL ROOFTOP EQUIPMENT AND USE PROPER SPACE # 2. ISLAND CONDENSER MAX FUSE 35 AMPS -- AC #14 ONE GROUND ONLY UNDER LUG 3. PANEL DIRECTORY TO BE CORRECT 4. MAX. 15 AMP FOR WALKINS PER DATA PLATES |
|
| 07/02/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. WORK NOT PER PLAN, PROVIDE SEALED LETTER FROM ARCHITECT FOR DELETIONS 2. GO OVER REST OF JOB AS DISCUSSED |