Permit: T06CM04508

Parcel: 117061900


Addresses:

216 E CONGRESS ST


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM04508

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/16/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
OK TO COVER ALL AREAS
06/20/2007 PLUMBING - INTERMEDIATE Partial Approval ABS UNDER FLOOR OK TO COVER
OK TO COVER WALLS
SCREW DOWN FLANGE
TEST ENTIRE ABS DWV - EITHER SECTIONAL OR COMPLETE
USE APPROVED HANGER AT EXPANSION TANK
06/12/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. NO PROVISION MADE FOR HOT WATER INSULATION
SEE PLUMBING NOTE #8
2. A BLAKE TEE IS LISTED FOR VERTICAL USE
MAY NOT BE INSTALLED HORIZONTALLY
3. FURNCO NOT APPROVED WITHIN A BUILDING
4. WILL PROVIDE A "PETITION OF APPEAL" FOR T&P RELIEF DRAIN AND COMPLETE REQUIREMENTS
5. PLEASE REDLINE ALL CHANGES TO THE PLAN