Permit: T06CM04508

Parcel: 117061900


Addresses:

216 E CONGRESS ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM04508

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/17/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CLEARANCE FOR SERVICE WILL BE SENT THIS MORNING TO TEP - DUE TO WORK LOAD & INSPECTION ROUTING INSPECTORS CANNOT ALWAYS ACCOMODATE TIMES. IF YOU WANT TO MEET WITH INSPECTORS LEAVE MSG. ON REQUEST FOR CALL AHEAD
07/09/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- SEE NOTE #1 LAST INSPECTION, PLEASE NOTIFY TEP AS TO CODE VIOLATION AND ALSO TRIP HAZARD.
- OK 1ST FLOOR WALLS
04/11/2007 ELECTRIC - INTERMEDIATE Denied 1. SEVERAL MISSING RECEPTACLES AS NOTED ON PLANS
2. SUPPORT ALL MC - BASEMENT, SEAL HOLES
3. RESUPPORT WH DISCONNECT IN UPRIGHT POSITION
4. RECEPTACLE IN CEILING 1ST FLOOR MISSING
5. PLANS CALL TO REMOVE PNL B
REVIEW PLANS AND INSTALL AS PER PLAN OR REVISE
04/10/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
There is no access to the site.| 920*
BUILDING LOCKED
03/20/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MAINTAIN WORKING CLEARANCES IN FRONT OF
PANEL 110.26
2. FILL UNUSED OPENING IN BOXES
3. MOVE JUNCTION BOX OUT TO EDGE OF DRYWALL OR INSTALL PLASTER RING.
4. SUPPORT CONDUITS AS PER CODE
5. WORK NOT INSTALLED AS PER PLANS
6. PLANS CALL FOR GROUNDING EQUIPMENT CONDUCTORS IN RACEWAYS.
03/13/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
There is no access to the site.| 920*
NO ACCESS TO WORK SITE 9:20