Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 10/04/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* OK TO CONTINUE 1. AT INTER. INSP. CHECK FOR DBL. CMST. STRAPS AT INTERIOR WALL BATH/DEN |
|
| 09/28/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | 1) SHEARWALL ENDS NEED TWO STUDS 2) DETAIL 3/DT2 RAFTER DEPTH AT PLUMB CUT 14" HOW DO YOU BLK AT THAT DEPTH (A DETAIL WOULD HELP) 3) FINISH NAILING THA HANGERS 2ND FLOOR BEAM 4) AT FRONT DOOR VERT. NAIL WALL TO 4 X 6 5) BROKEN TRUSS REAR (FLR TYPE) 6) PLAN CALLS FOR CMST COIL STRAP 3" WIDE 52" LONG (7) ON SHEAR PLAN |