Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T06CM04503

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
10/23/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
10/04/2006 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
OK TO CONTINUE
1. AT INTER. INSP. CHECK FOR DBL. CMST. STRAPS AT INTERIOR WALL BATH/DEN
09/28/2006 EXT METAL CLIPS/EXT SHEATHING Denied 1) SHEARWALL ENDS NEED TWO STUDS
2) DETAIL 3/DT2 RAFTER DEPTH AT PLUMB CUT 14" HOW DO YOU BLK AT THAT DEPTH (A DETAIL WOULD HELP)
3) FINISH NAILING THA HANGERS 2ND FLOOR BEAM
4) AT FRONT DOOR VERT. NAIL WALL TO 4 X 6
5) BROKEN TRUSS REAR (FLR TYPE)
6) PLAN CALLS FOR CMST COIL STRAP 3" WIDE 52" LONG (7) ON SHEAR PLAN