Permit: T06CM04502

Parcel: 141185830

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
06/22/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
- SOME FLEX DUCTS NOT SUPPORTED ADEQUATELY.
- SUPPORTS NEED TO BE EVERY 5'
- DUCTS NOT CONNECTED PER DETAIL ON PLANS
- WILL CHECK ON FINAL
- PROVIDE AUDIBLE & VISIBLE ALARMS ON DUCT SMOKE DETECTORS.
06/06/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE BACKING AROUND CEILING BOXES PRIOR TO SHEETROCK. CONDENSATE PIPING OK TO COMPLETE.