Permit: T06CM04502

Parcel: 141185830

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
07/25/2007 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
06/29/2007 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1) BONDING JUMPER IN DISCONNECT TO BE 1/0
2) NEED LETTER FROM ENGINEER ON CHANGE TO EMPT SIZE
3) SEAL OPENINGS IN SPARE EMT'S INTO PANELS