Permit: T06CM04502

Parcel: 141185830

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/25/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS & CEILING IN JANITORS CLOSET IN EXISTING
LONG REALTY SPACE
06/22/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECURE MC CABLE WITHIN 12" OF LIGHT JUNCTION BOX AT JANITORS CLOSET
2. PROTECT WIRES RUN IN STUD CHANNEL OR MOVE WIRES OUT OF CHANNEL. (JANITORS CLOSET)
3. REMOVE TEMP LIGHTING FROM CEILING
4. INSTALL TELEPHONE/DATA CABLE IN NEAT & WORKMAN LIKE MANNER. PROVIDE CABLE SUPPORTS EVERY 6'
DO NOT USE DUCT WORK, SPRINKLER PIPE, ETC FOR SUPPORT
06/20/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
There is no access to the site.| 920*
BUILDING LOCKED. NO ACCESS. KEY LEFT FOR INSPECTOR WOULD NOT UNLOCK DOOR 4:55 PM
06/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CEILINGS BATHROOMS
06/05/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK HALF WALLS AT RECEPTION/LOBBY RMS 123 & 124
2. OK HALF WALLS AT ROOM 122 OPEN AREA
3. OK CEILINGS AT RECEPTION/LOBBY RMS 123 & 129
4. PROVIDE ACCESS PANELS TO CONTRACTOR & JUNCTION BOX
ABOVE CEILING AT LOBBY ROOM 123
05/31/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS RMS 106, 108, 109, 110, 111, 112, 113, 114, 115, 116, 117
05/24/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK 2 - 2" PVC IN SLAB
2. OK 2 - 3/4" PVC IN SLAB
3. 3-GANG SWITCH BOX NOT GROUNDED
4. OK WALLS RMS. 100, 101, 102, 103, 105, 123, 124, 125, 126, 127, 128, 129, 130, 131, 132, 118, 119, 120, 121