Permit: T06CM04495

Parcel: 10510092A


Addresses:

4210 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T06CM04495

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
10/03/2008 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
09/23/2008 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
09/18/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1) THIS EVALUATION IS A ONE TIME ONLY UNTIL POLICY IS DETERMINED
09/11/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
PH# ON REQUEST NOT COMPLETE,
COULD NOT CALL CONTACT PERSON. RECALL, LEAVE MESSAGE
08/25/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. ENGINEER PLANS NOT AS INSTALLED
2. PROVIDE AN EFFECTIVE GROUND FAULT PATH FOR BUILDING STEEL
3. SUBMITTAL DRAWINGS INDICATE MODIFICATION OF SES
PROVIDE INSTRUCTIONS OR THIRD PARTY NRTL FIELD EVALUATION.
4. FINISH ANCHORING BACK OF SWITCHBOARD

*RECEIVED LETTER OF TORQUE
08/08/2008 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1. ANCHOR SWITCHGEAR TO CONCRETE PAD
2. PROVIDE LETTER OF TORQUE
3. NEED REVISION TO PLANS FOR CHANGE IN SERVICE AND SERVICE CONDUCTORS
4. HAVE 3 SECTION SUB-D LISTED 1 OF 1, 1 OF 2, 2 OF 2
PROVID INSTRUCTION OR MAY NEED FIELD EVALUATION
5. BOND BUILDING STEEL PROPERLY