Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T06CM04495
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/03/2008 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
09/23/2008 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* | |
09/18/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) THIS EVALUATION IS A ONE TIME ONLY UNTIL POLICY IS DETERMINED |
|
09/11/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* PH# ON REQUEST NOT COMPLETE, COULD NOT CALL CONTACT PERSON. RECALL, LEAVE MESSAGE |
|
08/25/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ENGINEER PLANS NOT AS INSTALLED 2. PROVIDE AN EFFECTIVE GROUND FAULT PATH FOR BUILDING STEEL 3. SUBMITTAL DRAWINGS INDICATE MODIFICATION OF SES PROVIDE INSTRUCTIONS OR THIRD PARTY NRTL FIELD EVALUATION. 4. FINISH ANCHORING BACK OF SWITCHBOARD *RECEIVED LETTER OF TORQUE |
|
08/08/2008 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1. ANCHOR SWITCHGEAR TO CONCRETE PAD 2. PROVIDE LETTER OF TORQUE 3. NEED REVISION TO PLANS FOR CHANGE IN SERVICE AND SERVICE CONDUCTORS 4. HAVE 3 SECTION SUB-D LISTED 1 OF 1, 1 OF 2, 2 OF 2 PROVID INSTRUCTION OR MAY NEED FIELD EVALUATION 5. BOND BUILDING STEEL PROPERLY |