Permit: T06CM04495

Parcel: 10510092A


Addresses:

4210 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T06CM04495

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
10/03/2008 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
05/01/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK REMAINDER SERVICE SECONDARY TRENCH COVER FROM "Y" TO X-FORMER - INSTALL WARNING RIBBON
03/27/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
INSTALL WARNING RIBBON MIN. 12" ABOVE SERVICE SECONDARY RACEWAYS OK TO COVER TO "Y"
INTERSECT AFTER THAT
HAVE 180 DEG. OF BENDS TO "Y"
03/24/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
CANNOT USE SOFT CORE FOR XFMR SECONDARYS
01/14/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. UFER COVERED/POURED WITHOUT INSPECTION

OK TO COVER SERVICE SECONDARY RACEWAYS - STUB TO ABOUT 10' FROM STRUCTURE WALL WITH 1 TURN UP 90 DEG. (3 - 3" PVC) CALL WHEN REST OF SECONDARY COMPLETE.