Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM04494
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/03/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/29/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED BY ELECTRICIAN PLEASE SCHEDULE WHEN THEY CAN ACCESS |
|
08/25/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FINISH ANCHORING BACK OF SWITCHBOARD 2. PROVIDE AN EFFECTIVE GROUND FAULT BATH FOR BUILDING STEEL 3. PANEL DIRECTORY TO BE AS PER 408.4 LEGIBLE AND NO ABBREVIATIONS 4. LIGHTING & EM LIGHTS NOT WORKING *RECEIVED LETTER OF TORQUE |