Permit: T06CM04494

Parcel: 10510092A


Addresses:

4206 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T06CM04494

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
09/03/2008 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
04/04/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK TO COVER AT BUILDING INTO SERVICE
"Y" IN TRENCH TO TRANSFORMER NOT COMPLETE
04/03/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
04/01/2008 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
WORK CALLED IN BEFORE COMPLETE
03/31/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK TO COVER SERVICE SECONDARY FROM Y IN TRENCH TO NORTHSIDE OF BUILDING
STILL NEED TO FIX KINKED RACEWAYS
INSTALL WARNING RIBBON WHEN YOU BACKFILL
03/26/2008 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR SERVICE SECONDARY RACEWAYS

1. NO MORE THAN 360 DEG. OF BENDS
2. NO KINKS IN RACEWAYS
3. INSERT RACEWAYS ALL THE WAY INTO COUPLING SO IT FITS SQUARE
03/24/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
CANNOT USE SOFT CORE FOR XFMR SECONDARYS
01/17/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*