Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. #10 GROUND TO JUNCTION BOXES WITH 30A CIRCUITS 2. INSTALL #10 GROUND TO A/C UNIT #2 3. INSTALL 3 POLE 60A BKR IN PANEL "PA" TO FEED TRANSFORMER "TPA" 4. PANEL A TO BE 100A MCB NO MLO 5. EXHAUST FANS NOT INSTALLED 6. LABEL BKR IN PANEL "P" FOR PANEL "PA" |