Permit: T06CM04470

Parcel: 11206424A


Addresses:

2545 N TUCSON BL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/24/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
06/22/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
SHALL SEE CORRECT TERMINATION OF FLUE VENT THRU ROOF PER MANUFACTURE
05/14/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
02/21/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
IS SYSTEM MEDIUM PRESSURE OR INCHES
1. SHALL PROVIDE GAS ISOMETRIC PLAN (CITY APPROVED) OF ENTIRE GAS SYSTEM WITH GAS PRESSURE OF SYSTEMS AND REGULATOR LOCATIONS.
2. SHALL PROVIDE CORRECT COMBUSTION AIR FOR 1600 CFH
3. VENTS FROM REGULATORS INDOORS MAY NEED TO BE TERMINATED AT BUILDING EXTERIOR.
4. TEE CONNECTION WITH PETE'S PLUG SHALL BE SHOWN ON APPROVED PLAN IF REQUIRED TO MONITOR GAS SYSTEM. SEE MECHANICAL INSPECTION SHEET FOR ADDITIONAL REQUIREMENTS.