Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2007 | PLUMBING - GAS PRESSURE TEST | Approved | ||
| 05/14/2007 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* HAVE YOUR 5 LB. TO 1 LB. REGULATOR ON SITE WITH SHUT OFF VALVE INSTALLED TEST FOR FURNACES/WATER HEATER PIPING OK 1. SHALL INSTALL 1 POUND X 7" REGULATOR WITH APPROVED GAS SHUT OFF VALVE JUST UPSTREAM OF REGULATOR AND RUN VENT FROM REGULATOR 5' FROM ANY OPENABLE WINDOW OR AIR INTAKE WITH APPROVED GAS PIPING MATERIAL. 2. TEST ON PIPING TO CREMATORY (PARTIAL) SEE NOTE #4 FROM 2/21/07 INSPECTION OR REMOVE THAT TEE FITTING & RETEST (2) VENT FROM REGULATOR ON CREMATORY SHALL BE APPROVED METAL PIPING TERMINATING 5' FROM DOOR OR ANY AIR INTAKE, TRACER IN UPWARD DIRECTION AND TERMINATE WITH WEATHER 90 DEG. AND VERMIN SCREEN ON OPENING. 3. VENTS FROM WATER HEATER/FURNACES SHALL BE INSTALLED CORRECTLY THRU ROOF WITH APPROVED VENT MATERIAL AND VENT CAP MINIMUM 2' ABOVE ANY AIR INTAKE. NOTE: CONDENSATE SHALL GO TO PLANTER AREA |
|
| 02/21/2007 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* |