Permit: T06CM04452

Parcel: 10408075P


Addresses:

4439 N ORACLE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/15/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/09/2006 ELECTRIC - FINAL Partial Approval OK FOR TEMP C OF O FOR STOCKING ONLY
11/09/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PARTIAL INSPECTION ONLY
1. MAKE G.E.C ELECTRICALLY CONTINUOUS OR RUN IN PLASTIC
NEC 250.64(E)
2. CORDS TO BE 12 GA MINIMUM AND PROVIDE STRAIN RELIEF AND 20 AMP RATED RECEPTACLE - NEC 400.5, 400.10, 210.21 (B)
3. SELF TAP SCREWS NOT ALLOWED FOR EQUIPMENT GROUND CONNECTION -- NEC 250.8
4. SECURE ALL MC FOR TRACK LIGHTING WITHIN 12" OF TERMINATIONS NEC 330.0
5. NEED ISOLATED AND EQUIPMENT GROUND @ P.O.S RECEPTACLES -- NEC 250
6. AT P.O.S PANEL -- STRAP TRANSFORMER FLEX, FIX TRANSFORMER FLEX CONNECTION, INSTALL K.O BLANKS IN PANEL.
7. FINISH TROUBLESHOOTING, FIXTURES AND BULB INSTALLATION.
8. HAVE DEAD/SHORTED BRANCH CKT'S
9. MAKE SURE ALL EMERGENCY LIGHTING IS WORKING AND PER PLAN (NEC 700.12) AND AIM LIGHTS DOWN AND OUT.

NOTE: CORRECTIONS TO BE COMPLETED BEFORE THANKSGIVING AND APPROVED.

OK TO OCCUPY FOR THE PURPOSE OF STOCKING/SET UP
11/08/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*