Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/09/2006 | ELECTRIC - FINAL | Partial Approval | OK FOR TEMP C OF O FOR STOCKING ONLY | |
| 11/09/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* PARTIAL INSPECTION ONLY 1. MAKE G.E.C ELECTRICALLY CONTINUOUS OR RUN IN PLASTIC NEC 250.64(E) 2. CORDS TO BE 12 GA MINIMUM AND PROVIDE STRAIN RELIEF AND 20 AMP RATED RECEPTACLE - NEC 400.5, 400.10, 210.21 (B) 3. SELF TAP SCREWS NOT ALLOWED FOR EQUIPMENT GROUND CONNECTION -- NEC 250.8 4. SECURE ALL MC FOR TRACK LIGHTING WITHIN 12" OF TERMINATIONS NEC 330.0 5. NEED ISOLATED AND EQUIPMENT GROUND @ P.O.S RECEPTACLES -- NEC 250 6. AT P.O.S PANEL -- STRAP TRANSFORMER FLEX, FIX TRANSFORMER FLEX CONNECTION, INSTALL K.O BLANKS IN PANEL. 7. FINISH TROUBLESHOOTING, FIXTURES AND BULB INSTALLATION. 8. HAVE DEAD/SHORTED BRANCH CKT'S 9. MAKE SURE ALL EMERGENCY LIGHTING IS WORKING AND PER PLAN (NEC 700.12) AND AIM LIGHTS DOWN AND OUT. NOTE: CORRECTIONS TO BE COMPLETED BEFORE THANKSGIVING AND APPROVED. OK TO OCCUPY FOR THE PURPOSE OF STOCKING/SET UP |
|
| 11/08/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |