Permit: T06CM04452

Parcel: 10408075P


Addresses:

4439 N ORACLE RD

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
11/15/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
11/07/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK REMAINDER DROP CEILING COVER
11/03/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO COVER NORTH SIDE SUSPENDED CEILING
EAST SIDE LOW VOLTAGE STILL NEEDS WORK.
11/02/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :$
1) SUPPORT WIRES NEED TO BE SECURED AT BOTH ENDS DO NOT CALL FOR INSPECTION BEFORE ALL CORRECTIONS ARE MADE
11/01/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
WILL CALL WHEN READY
10/31/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
RECEIVED CHK#1128
BRAD 1/2 256-3247

1. REMOVE TEMP WIRING ABOVE CEILING
2. TAG OR REMOVE ALL ABANDONED LOW VOLTAGE WIRING
3. SECURE ALL FIXTURES TO GRID
4. SUPPORT WIRES FOR GRID NOT TO BE USED TO SUPPORT OTHER EQUIPMENT.
5. LOW VOLTAGE WIRING TO BE INDIVIDUALLY SUPPORTED
(AT BOTH ENDS)
6. HAVE OVERFILLED J-BOXES
7. CONNECT ALL EQUIPMENT GROUNDS IN J-BOXES
INSPECTION FOR NORTH AND EAST DROP CEILING AREAS ONLY