Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/07/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK REMAINDER DROP CEILING COVER |
|
| 11/03/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO COVER NORTH SIDE SUSPENDED CEILING EAST SIDE LOW VOLTAGE STILL NEEDS WORK. |
|
| 11/02/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :$ 1) SUPPORT WIRES NEED TO BE SECURED AT BOTH ENDS DO NOT CALL FOR INSPECTION BEFORE ALL CORRECTIONS ARE MADE |
|
| 11/01/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* WILL CALL WHEN READY |
|
| 10/31/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* RECEIVED CHK#1128 BRAD 1/2 256-3247 1. REMOVE TEMP WIRING ABOVE CEILING 2. TAG OR REMOVE ALL ABANDONED LOW VOLTAGE WIRING 3. SECURE ALL FIXTURES TO GRID 4. SUPPORT WIRES FOR GRID NOT TO BE USED TO SUPPORT OTHER EQUIPMENT. 5. LOW VOLTAGE WIRING TO BE INDIVIDUALLY SUPPORTED (AT BOTH ENDS) 6. HAVE OVERFILLED J-BOXES 7. CONNECT ALL EQUIPMENT GROUNDS IN J-BOXES INSPECTION FOR NORTH AND EAST DROP CEILING AREAS ONLY |