Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T06CM04446
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/09/2008 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
06/24/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* | |
06/20/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BELL ENDS NEEDED TO PROTECT CONDUCTORS 251.46 & 300.4 2. PROVIDE LETTER FOR TORQUE 3. CONDUCTOR TO ENTER IN SECTION SERVED 408 .3 4. NEED LETTER FROM ENGINEER FOR GROUNDING ELECTRODE SYSTEM 5. NEED THIRD PARTY EVALUATION FROM NRTL TO INSTALL BREAKERS SECTION #4 6. DRIVE GROUND RODS FLUSH 7. PLEASE VERIFY IF CABLE BRACING IS NEEDED 8. ONLY ONE CONDUCTOR PER LUG |
|
06/19/2008 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* |