Permit: T06CM04446

Parcel: 137055110

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T06CM04446

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
07/09/2008 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
06/24/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
06/20/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BELL ENDS NEEDED TO PROTECT CONDUCTORS
251.46 & 300.4
2. PROVIDE LETTER FOR TORQUE
3. CONDUCTOR TO ENTER IN SECTION SERVED 408 .3
4. NEED LETTER FROM ENGINEER FOR GROUNDING ELECTRODE SYSTEM
5. NEED THIRD PARTY EVALUATION FROM NRTL TO INSTALL BREAKERS SECTION #4
6. DRIVE GROUND RODS FLUSH
7. PLEASE VERIFY IF CABLE BRACING IS NEEDED
8. ONLY ONE CONDUCTOR PER LUG
06/19/2008 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*