Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM04437
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/13/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/12/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TIE OFF - DO NOT USE TIE WIRE USE #9 2. LABEL PNLS O/S PERMANENTLY 3. NEUTRAL BAR AT PNL B TO BE LIFTED OR SURFACE 4. INSTAHOT WH NEEDS TO BE SWITCHED OR HAVE A LOCK OUT AT PNL. |
|
12/20/2006 | ELECTRIC - FINAL | Partial Approval | PROVIDE CLARIFICATION FROM ARCHITECT FOR EMERGENCY LIGHTING OK TO OCCUPY PHASE ONE | |
12/20/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |