Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM04431
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/28/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
11/22/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) ALL PLUMBING INSTALLED PER PLAN EXCEPT FOR CONDENSATE CONNECTION TO SINK 2) APPROVED LOCATIONS FOR A/C CONDENSATE ARE LAVITORY TALL PIECES OR OPEN RECEPTORS. THERE ARE BATHROOMS AND MOP SINKS LOCATED ON EVERY FLOOR |
|
11/21/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TWO P-TRAPS ON ONE TRAP ARM IS NOT ALLOWED. A DISHWASHER AG FITTING WOULD BE ACCEPTABLE WITH THIS UNIT WHICH HAS A PUMPED ICE BIN DRAIN WITH NO CONDENSATE FROM THIS EQUIPMENT. BE SURE THERE ARE NO KINKS IN DRAIN TUBING. 2. THE CONDENSATE FROM THE AIR CONDITIONING UNIT DOES REQURIE AN APPROVED RECEPTOR. HAVE ARCHITECT ADDRESS THIS CONDITION AND PROVIDE INSTRUCTION. |
|
11/17/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CONDENSATE CONNECTION TO BREAKROOM SINK IS BACKPITCHED AND HOLDING WATER -- PROVIDE APPROVED RECEPTOR FOR CONDENSATE DRAIN. 2. ONLY ONE SLIP NUT DOWNSTREAM OF P-TRAP 3. WATER TEST SINK, CLEAN UP SPILL ON CABINET BOTTOM. 4. HW NOT WORKING -- INSTALL INSTA-HOT PER PLAN. 5. ICE MAKER REQUIRES A 1" AIR GAP. |