Permit: T06CM04431

Parcel: 12709011E

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM04431

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/22/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
11/21/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/17/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO TILE
1. CHECK LAST STUFF ON FINAL (HALL AND EXIST VDV)
11/16/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FIXTURES, MC CABLES AND CONDUITS EXCEPT ROOM 128
1. FINISH VDV CABELING PER 725.3 & 6, 760.3 & 6, 770.3 & 6
800.3 & 6
11/15/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. VDV CABELING TO BE SECURED TO TRAY AT EXITING OF TRAY.
2. MC CABLE TO BE INDEPENDENTLY SUPPORTED 300.11
3. WE HAVE BOX OVERFILL
4. SUPPORT WIRES NEEDED FOR ALL LIGHT FIXTURES.

OK ROOM 125