Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/15/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/11/2007 | FRAMING | Partial Approval | IVRS - Inspection :*. 1) REAR BLDG: OK TO INSULATE AND SHEETROCK REAR PORTION OF BLDG 2) CLARIFY PLOT PLAN ONLY 1 UNIT ON THIS PROPERTY PLOT PLAN APPROVED WITH 2 UNITS. 1-ADDRESS CLARIFY PRIOR TO NEXT INSPECTION |
|
| 05/10/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIREBLOCK FURR DOWN CEILINGS 2) PLAN CALLS FOR TJI 25 JOISTS-TJI 210 INSTALLED 3) INSTALL BANG PLATES THROUGHOUT 4) FILL IN SOLIDLY UNDER TJI JOISTS BEARING 5) INSTALL TIMBER STRAND LSL BLOCKING 6) DBL 2 X 6 POST UNDER 2-2 X 10 HEADER REQUIRED 7) STRAP ALL HEADERS AT BEARING 8) BOTTOM OF LAP SIDING VARIED FROM LAP BOTTOM WOOD PLATE 9) BOTTOM OF LAP SIDING TO BE MINIMUM 6" ABOVE GRADE 10) FILL IN SOLIDLY UNDER DBL 2 X 10 BEARING 11) LAYOUT REMODEL FRONT NOT PER PLAN 12) COURT YARD DECK, PORCH COVERED PARKING INCOMPLETE 13) STOPPED INSPECTION-COMPLETE ALL TRADES AND RECALL |