Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T06CM04417
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/02/2009 | MECHANICAL - INTERMEDIATE | Approved | ||
12/14/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* GALLERY WOMENS RESTROOM OK TO ROCK |
|
12/11/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO TILE SKY BISTRO - WEST INSTALL REGISTER AT VAV C042 WRAP SUPPLY DUCT IN GALLERY RESTROOM PROVIDE SUPPORT ON DUCT TO VAV WEST END INSULATE HWS/HWR AT BAR AREA COMPLETE ALL HWS/HWR INSULATION SEAL VAV INLETS INSTALL CAPS AT DRAINS |
|
11/07/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WEST CONCOURSE MENS RESTROOM OK |
|
11/01/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - WEST CONCOURSE MENS RESTROOM - NO STENCILS ON F.D ACCESS DOORS - FIRE DAMPER FLANGE RINGS NOT PROPERLY INSTALLED - DUCT SEAL ON SPIN IN COLLARS |
|
10/29/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO TILE EAST CONCOURSE |
|
10/24/2007 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* EAST CONCOURSE NOT READY DO NOT SUPPORT FLEX DUCT FROM E.M.T PROVIDE HANGERS WITH SADDLES ON ANY FLEX DUCT IN EXCESS OF 5' IN LENGTH SEE LIST DATED 10/10/07 WEST NOT READY |
|
10/10/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO TILE BORDERS JEFF 940-1698/404-0448 FINISH INSULATING ROUND DUCT AT DIFFUSERS SEAL ALL JOINTS REPAIR TORN INSTALLATION ON DUCT WORK REPLACE COVERS AT UNITS PROVIDE SADDLES ON FLEX PER 2M4.01-11 FINISH INSULATION ON REVENT COIL PIPING |
|
08/01/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHECKED HOT WATER PIPING TO VAV'S EAST CONCOURSE ABOVE CEILING. OK TO PROCEED. OK TO SHEETROCK RESTROOMS FIS AREA |
|
07/12/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* COULD NOT LOCATE SUPERINTENDENT NOBODY RETURNED MY CALL PLEASE LEAVE A CONTACT NUMBER WHEN SCHEDULING INSPECTIONS. |
|
06/22/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO SHEETROCK RESTROOMS EAST CONCOURSE |
|
06/20/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO SHEETROCK RESTROOMS WEST CONCOURSE |
|
06/12/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHECKED 100 PSI TEST ON WATER PIPING TO FAN COIL OK TO INSULATE |
|
06/08/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROVIDE 100 PSI TEST ON ALL WATER PIPING TO FAN COIL #7 FINISH SOLDERING DRAIN FITTINGS ABOVE CORRIDOR DO NOT DRIP SECONDARY DRAINS ONTO CEILING TILES. |
|
05/18/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* EAST COURSE MECH UP AREA WORK ABOVE GRID/CEILING TILES OK OK TO COVER |
|
05/15/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* F I S AREA LOWER LEVEL, VAV #68 SUSPENDED/SHT. MTL. DUCT, OK TO WRAP PIPING HYDRONIC |
|
04/06/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CHECKED HOT AND COLD WATER PIPING TO FC 4, 5, 6 & 8 2) OK TO INSULATE |
|
02/15/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUSPENDED ROUGH DUCT. OK TO PROCEED RABBIT 631-4401 |
|
02/08/2007 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |