Permit: T06CM04417


Addresses:

7250 S TUCSON BL

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/02/2009 MECHANICAL - INTERMEDIATE Approved
12/14/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
GALLERY WOMENS RESTROOM OK TO ROCK
12/11/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO TILE SKY BISTRO - WEST

INSTALL REGISTER AT VAV C042
WRAP SUPPLY DUCT IN GALLERY RESTROOM
PROVIDE SUPPORT ON DUCT TO VAV WEST END
INSULATE HWS/HWR AT BAR AREA
COMPLETE ALL HWS/HWR INSULATION
SEAL VAV INLETS
INSTALL CAPS AT DRAINS
11/07/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
WEST CONCOURSE MENS RESTROOM OK
11/01/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
- WEST CONCOURSE MENS RESTROOM
- NO STENCILS ON F.D ACCESS DOORS
- FIRE DAMPER FLANGE RINGS NOT PROPERLY INSTALLED
- DUCT SEAL ON SPIN IN COLLARS
10/29/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO TILE EAST CONCOURSE
10/24/2007 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
EAST CONCOURSE NOT READY
DO NOT SUPPORT FLEX DUCT FROM E.M.T
PROVIDE HANGERS WITH SADDLES ON ANY FLEX DUCT IN EXCESS OF 5' IN LENGTH SEE LIST DATED 10/10/07

WEST NOT READY
10/10/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO TILE BORDERS

JEFF 940-1698/404-0448

FINISH INSULATING ROUND DUCT AT DIFFUSERS
SEAL ALL JOINTS
REPAIR TORN INSTALLATION ON DUCT WORK
REPLACE COVERS AT UNITS
PROVIDE SADDLES ON FLEX PER 2M4.01-11
FINISH INSULATION ON REVENT COIL PIPING
08/01/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
CHECKED HOT WATER PIPING TO VAV'S EAST CONCOURSE
ABOVE CEILING. OK TO PROCEED.
OK TO SHEETROCK RESTROOMS FIS AREA
07/12/2007 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
COULD NOT LOCATE SUPERINTENDENT
NOBODY RETURNED MY CALL
PLEASE LEAVE A CONTACT NUMBER WHEN SCHEDULING INSPECTIONS.
06/22/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO SHEETROCK RESTROOMS EAST CONCOURSE
06/20/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO SHEETROCK RESTROOMS WEST CONCOURSE
06/12/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
CHECKED 100 PSI TEST ON WATER PIPING TO FAN COIL
OK TO INSULATE
06/08/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
PROVIDE 100 PSI TEST ON ALL WATER PIPING TO FAN COIL #7
FINISH SOLDERING DRAIN FITTINGS ABOVE CORRIDOR
DO NOT DRIP SECONDARY DRAINS ONTO CEILING TILES.
05/18/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
EAST COURSE MECH UP AREA
WORK ABOVE GRID/CEILING TILES OK
OK TO COVER
05/15/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
F I S AREA LOWER LEVEL, VAV #68
SUSPENDED/SHT. MTL. DUCT, OK TO WRAP
PIPING HYDRONIC
04/06/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CHECKED HOT AND COLD WATER PIPING TO FC 4, 5, 6 & 8
2) OK TO INSULATE
02/15/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
SUSPENDED ROUGH DUCT. OK TO PROCEED
RABBIT 631-4401
02/08/2007 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*