Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM04417
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/22/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/24/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CAN LIGHTS REQUIRE SEISMIC WIRES, MC CABLES TO BE SUPPORTED WITHIN 12" OF TERMINATION AND AT 6' INTERVALS, PER CODE. SEISMIC WIRES USE AS SUPPORT TO BE TIED OF AT BOTH ENDS, DO NOT USE SEISMIC INTENDED TO SUPPORT GRID. 300-11 NEC DATA CABLES LAYLINE ON GRID 2) A REINSPECTION FEE IS ASSESSED, THIS IS THE THIRD INSPECTION FOR THIS AREA-COFFEE BAR AT WEST CONCOURSE |
|
02/20/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* - OK RESTROOMS FINALS IN GALLERY AREA - OK ABOVE CEILINGS IN F.I.S AREA |
|
12/05/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* - OK AREAS AT GATE 9-10 TO GOLF SHOP AT GATE #7 FOR ABOVE CEILING, EXCEPT THE COFFEE BAR. - OK FINAL FOR MENS RESTROOMS WEST CONCOURSE |
|
11/19/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK WALLS AT WOMEN'S RESTROOM AND GALLERY AREA 2) OK FINAL FOR EAST CONCOURSE WOMEN'S BATHROOM |
|
08/23/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK 3RD FLOOR MEZZ WEST, EAST CONCOURSE RESTROOMS, EAST & WEST CONCOURSE RESTROOMS & TICKETING |