Permit: T06CM04417


Addresses:

7250 S TUCSON BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04417

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/22/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/24/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CAN LIGHTS REQUIRE SEISMIC WIRES, MC CABLES TO BE SUPPORTED WITHIN 12" OF TERMINATION AND AT 6' INTERVALS, PER CODE. SEISMIC WIRES USE AS SUPPORT TO BE TIED OF AT BOTH ENDS, DO NOT USE SEISMIC INTENDED TO SUPPORT GRID. 300-11 NEC DATA CABLES LAYLINE ON GRID
2) A REINSPECTION FEE IS ASSESSED, THIS IS THE THIRD INSPECTION FOR THIS AREA-COFFEE BAR AT WEST CONCOURSE
02/20/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
- OK RESTROOMS FINALS IN GALLERY AREA
- OK ABOVE CEILINGS IN F.I.S AREA
12/05/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
- OK AREAS AT GATE 9-10 TO GOLF SHOP AT GATE #7 FOR ABOVE CEILING, EXCEPT THE COFFEE BAR.
- OK FINAL FOR MENS RESTROOMS WEST CONCOURSE
11/19/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK WALLS AT WOMEN'S RESTROOM AND GALLERY AREA
2) OK FINAL FOR EAST CONCOURSE WOMEN'S BATHROOM
08/23/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK 3RD FLOOR MEZZ WEST, EAST
CONCOURSE RESTROOMS, EAST & WEST
CONCOURSE RESTROOMS & TICKETING