Permit: T06CM04417


Addresses:

7250 S TUCSON BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM04417

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/22/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/30/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- SUPPORT MC CABLE PER NEC
WITHIN 12" OF TERMINATION AND AT 6' INTERVALS,
DO NOT USE GRID WIRES INTENDED TO SUPPORT GRID SYSTEM.
01/28/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
METER CONTROL CABINET FOR THE BAGGAGE BELT IN VIOLATION OF 110-26 NEC
DEDICATED & WORKING SPACE FIS AREA
01/04/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. COFFEE BAR AT GATE 7 & 14 (IKE'S) ABOVE CEILING HAS MULTIPLE CODE VIOLATIONS SUCH AS UNSUPPORTED MC CABLES, LIGHT FIXTURES, OPEN J-BOXES, MC CABLE NOT TERMINATED PROPERLY, UNGROUNDED J-BOXES, DOUBLE DUPLEX RECEPT. HANGING OUT OF GRID
2. NO SEISMIC WIRES ON FIXTURES IN GRID (IKE'S)
3. OK ROUGH FOR MUFFIDS & PHONES AREA WEST CONCOURSE AT RESTROOMS, OK CONTINUATION OF GRID CEILING FROM DESERT HOUSE TO BOTTOM RAMP
4. CALL FOR INSPECTION BF TAGGED AREAS ABOVE GRID
12/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH FOR PHONES, ELECTRIC AT EAST CONCOURSE
FLIGHT INFO BOARDS
11/09/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK MENS RESTROOM WALLS AT GALLERY
11/01/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/24/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO CLEAR INCR - CALLED INTO KATHY CLARK 12:15 PM
FOR TAA 63 FEEDER
RECEIVED SES TEST RESULTS ALSO FOR BUSS & TAP BOXES
OK WEST CONCOURSE MENS RESTROOM WALLS
OK ABOVE CEILING FOR NEW RESTROOMS EAST CONCOURSE & LOBBY'S & SECURITY, VESTIBULE AT GATE #21
10/10/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS FIS AREA & HARD LIDS
OK EAST BAGGAGE LEVEL CORRIDOR
OK IDF #10
OK GATE #23 TO #24 ABOVE CEILING
TIE UP DATA/LV CABLE IN A WORKMANSHIP LIKE MANNER
10/08/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS EAST CONCOURSE WOMENS RESTROOMS
09/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- EAST CONCOURSE ELECTRIC ROOM MAIN SES (NEW)
- BOND BLD. STEEL PER 250.104
06/22/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALLS AT NEW HOLDING AREA
2. OK RESTROOM ABOVE CEILINGS EAST CONCOURSE
05/30/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. EAST TICKET RESTROOM AREA ROUGH
2. F15 RESTROOM EAST
05/01/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK U.G FEEDERS & GROUNDING FOR NEW SES IN EAST ELECTRICAL ROOM.
04/30/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
CALLED 730-1414 PER REQUEST -- NO RETURN CALL
INSPECTOR LEFT MSG. RECALL INSP.
04/09/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PLEASE RECALL INSPECTION AND LEAVE MESSAGE WITH PHONE NUMBER OF CONTACT PERSON
03/07/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH, WEST RESTROOMS AT DESERT NEWS GIFT SHOP
02/15/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS 3RD FLOOR MEZZ.