Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM04413
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/31/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE OK FOR FINAL |
|
10/27/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* DUCT SMOKE DETECTORS NOT SHUTTING DOWN FAN. |
|
10/26/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* FIRE CAULK AROUND FIRE DAMPERS AS NEEDED. DO NOT SUPPORT FLEX DUCT WITH WIRE. PROVIDE AIR BALANCE REPORT. PERMANENTLY I.D UNIT ON ROOF NEED TO TEST DUCT SMOKE DETECTORS UNIT NOT FUSED CORRECTLY |