Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/27/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FIXTURES NOT LISTED AS JUNCTION BOX ONLY PASS THROUGH. 2. FINISH SUPPORTING FIXTURES 3. FILL UNUSED OPENINGS 4. SUPPORT VDV CABLEING 725.6 & BOX 5. BONDING NEEDING PER 250.97 AT 250 OR GREATER 6. ONLY ONE CONDUCTOR PER TERMINATION 7. USE CORRECT FUSES |
|
| 10/26/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |