Permit: T06CM04404

Parcel: 140550680

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
11/14/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
11/09/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WIND BRACE SOUTH SIDE ? MISSING NAIL
2) ROOF CLIP MISSING SOUTH WALL
3) LET IN BRACE MISSING SOUTH WALL
4) FHA STRAPS OR PROTECTION PLATES WHERE BOTTOM PLATE NOTCHED FOR PLUMBING OUTER WALLS
5) ANCHOR BOLTS NEED TO BE 1/2 ? NOT 3/8
6) NEED 3 NAILS IN CABIN TIED CORNERS
7) STRAP CORNERS WITHOUT CABING TIES
8) ROOF NAILING AT SEAMS NEEDS MORE NAILS VARIOUS PLACES ON ROOF
11/08/2006 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*