Inspection History Details
Inspection Status: Approved
Inspection History: SITE - SEWER
Permit Number - T06CM04395
Inspection Description - SITE - SEWER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/18/2008 | SITE - SEWER | Approved | ||
02/27/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 4" SDR 35 BLDG. SEWER INSTALLED PER REDLINES OK TO COVER SUBJECT TO APPROVAL OF P.O.C |
|
02/01/2008 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* 1. DIRT PILES HAVE NOT BEEN REMOVED SITE UTILITY PLAN CALLS FOR 65 L.F TO BE INSTALLED AT 6.30% SLOPE - 40 L.F AT 6.30% SLOPE AND CLEANOUT INVERTS. 2. CONTRACTOR TO PAY REINSPECTION FEE |
|
01/29/2008 | SITE - SEWER | Denied | IVRS - Inspection : See detailed listing on site.| 999* ONE SECTION OF PIPE PARTIALLY COVERED W/DIRT HAS BACKPITCH. REMOVE DIRT PILES, CORRECT SLOPE. UNLESS 1% IS SPECIFIED ON YOUR PLAN. SEC 708 REQUIRES 2% SLOPE I SEE NO STRUCTURAL CONDITIONS PREVENTING YOU FROM INSTALLING PER 708 CONTINUED DENIED INSPECTIONS MAY RESULT IN REINSPECTION FEES |
|
01/28/2008 | SITE - SEWER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BACKPITCH ON SDR, PROVIDE UNIFORM SLOPE @ 1/4" PER FOOT 2. NO PRIMER ON PVC GLUE JOINT 3. DITCH WET 4. ALL FITTINGS SHALL BE INSTALLED IN THE DIRECTION OF FLOW (WILL ACCEPT BULLHORNS AT BUILDING SEWER CONNECTION ONLY) 5. REMOVE ROCKS |