Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2008 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 04/18/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO POST POWER BOND WITH CITY OF TUCSON 2. BONDING CONDUCTOR FOR SERVICE SECONDARY RACEWAYS IS UNDERSIZED - NEC 250.102C 3. BOND BUILDING STEEL - NEC 250.104C 4. IDENTIFY SERVICE DISCONNECTS AS TO WHAT METER THEY SERVE 5. INSTALL FUSES FOR OWNERS MANUAL & IDENTIFY "OWNERS PANEL" |