Permit: T06CM04394

Parcel: 126060060


Addresses:

925 N COLUMBUS BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/31/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/22/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUND METAL BOXES
2) TERMINATE ROMEX IN EXHAUST FANS
3) MISSING OUTLET AT EAST WALL BY KITCHEN DOOR
4) GAS BOND MUST BE AT EXPOSED LOCATION
5) EXHAUST FAN REQUIRED PER CODE IN LAUNDRY ROOM
6) SMOKE DETECTOR WITHIN 3' OF FORCED AIR REGISTER MASTER BEDROOM
05/17/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LOOSE WIRE BY DOOR TO HOUSE
2) GROUND METAL BOXES
3) PORCH METAL BOXES NOT APPROVED TO SUPPORT FANS
4) CHECK WITH TEP FOR TRENCH REQUIREMENTS FROM ELECTRIC SERVICE TO POLE
05/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*