Permit: T06CM04392

Parcel: 13104410A


Addresses:

5025 E 29TH ST


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T06CM04392

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/20/2006 BUILDING - FINAL Approved IVRS - Inspection :*
10/20/2006 BUILDING - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
PLEASE PAY REINSPECTION FEE AT 201 N. STONE
TAKE CARE OF ITEMS 1 & 2 NOTED ON 10/3/06
10/03/2006 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1. LEVEL LANDING REQUIRED @ EXTERIOR OF ACCESSIBLE RESTROOMS
2. SPLIT FRONT TOILET SEATS REQUIRED ON ALL TOILETS.
3. DEADBOLT ON ACCESSIBLE PATH (REAR DOOR OF TENANT SPACE) MUST BE NO HIGHER THAN 48"
4. DEADBOLT ON FRONT DOOR TO BE NO HIGHER THAN 48" OR PUT UP SIGN "THIS DOOR TO REMAIN UNLOCKED..."
5. GRAB BARS IN RESTROOMS TO BE INSTALLED PER
ANSI 117.1 SECTION 604.5
09/25/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. POST ADDRESS DISPLAY PER P.C.Z.O 18.83.050
(ATTACHED SHEET)
2. DOUBLE BOWL SINK NOT SHOWN ON PLAN AND NOT INSTALLED PER CODE.
A. YOU CAN'T HAVE 2 FIXTURES ON SAME TRAP ARM.
B. YOU NEED TO VENT SINK TRAP ARM WITHIN 5' OF TRAP. YOU MAY USE AN A.A.V IN THIS APPLICATION.
3. WHEN WILL DELTA 1 REVISIONS (KEYNOTE 9, 10) BE IN PLACE? PLEASE PROVIDE APPROVED PLANS/PERMITS FOR ADA RESTROOMS. ADA RESTROOMS DO NOT MEET CHAPTER 11 REQUIRMENTS FOR ACCESSIBILITY.