Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM04387
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
07/02/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
06/27/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
12/11/2007 | ELECTRIC - INTERMEDIATE | Denied | 1. PROPERLY GROUND EQUIPMENT AND TIGHTEN GROUND SCREWS 2. CLOSE ALL UNUSED OPENINGS IN J-BOXES, FIXTURES 3. IDENTIFY WHITE USED AS HOT AT ALL LOCATIONS CONDUCTOR IS ACCESSIBLE 4. NEED PROTECTIVE BUSHING FOR CONDUCTORS ENTERING FIXTURES 5. CLEAN UP MC IN ATTIC - TO BE SECURED WITHIN 12" OF TERMINATIONS, EVERY 6' RAN NEAT AND WORKMAN LIKE 6. LOADS TO ORIGINATE PER PLAN 7. PLANS SHOW A 1:5 HP 3 PHASE EX. MOTOR, ALSO NEED DISCONNECT FOR MOTOR |
|
12/07/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |