Permit: T06CM04386

Parcel: 10602299A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04386

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/18/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/13/2006 ELECTRIC - FINAL Partial Approval OK PER SHEET -TCO APPROVED BY STEVE LONG
10/13/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. REMOVE PAINT UNDER CLAMPS & SECURE GEC TO STRUCTURE, TIGHTEN ALL CLAMP SCREWS.
2. TWO EMERGENCY LIGHTS NOT WORKING.
3. WORK IN PROGRESS

OK TO OCCUPY
10/12/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. FOR FINAL REDO PNL SCHEDULE
2. FINISH CORRECT GRADING CT CAN
3. INSTALL PNL COVER PNL A
4. PNL CC CORRECTLY IDENTIFY PNL (LOCATION RM#)
5. TIE IN WATER HEATER -- TAPE WIRES CORRECTLY
6. FINISH TIE IN FOR FURNITURE ELECT.
7. HW DISCONNECTS TO BE TIED IN
8. AC DISCONNECTS CORRECT WIRING #5 ENTERING CAN
AC DISCONNECTS CORRECT WIRING #4 BOTTOM ENTRY

RESECURE LOOSE DISCONNECTS NEED ID

NOT A FINAL INSPECTION -- PROGRESS ONLY
10/10/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
- WORK IN PROGRESS, CALL WHEN COMPLETE
- ALSO, NEED TO REPAIR/REPLACE GROUNDING ELECTRODE CONDUCTOR FOR SERVICE.
- CEILING TILES INSTALLED WITHOUT INSPECTION.