Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM04386
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/18/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/13/2006 | ELECTRIC - FINAL | Partial Approval | OK PER SHEET -TCO APPROVED BY STEVE LONG | |
10/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. REMOVE PAINT UNDER CLAMPS & SECURE GEC TO STRUCTURE, TIGHTEN ALL CLAMP SCREWS. 2. TWO EMERGENCY LIGHTS NOT WORKING. 3. WORK IN PROGRESS OK TO OCCUPY |
|
10/12/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FOR FINAL REDO PNL SCHEDULE 2. FINISH CORRECT GRADING CT CAN 3. INSTALL PNL COVER PNL A 4. PNL CC CORRECTLY IDENTIFY PNL (LOCATION RM#) 5. TIE IN WATER HEATER -- TAPE WIRES CORRECTLY 6. FINISH TIE IN FOR FURNITURE ELECT. 7. HW DISCONNECTS TO BE TIED IN 8. AC DISCONNECTS CORRECT WIRING #5 ENTERING CAN AC DISCONNECTS CORRECT WIRING #4 BOTTOM ENTRY RESECURE LOOSE DISCONNECTS NEED ID NOT A FINAL INSPECTION -- PROGRESS ONLY |
|
10/10/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* - WORK IN PROGRESS, CALL WHEN COMPLETE - ALSO, NEED TO REPAIR/REPLACE GROUNDING ELECTRODE CONDUCTOR FOR SERVICE. - CEILING TILES INSTALLED WITHOUT INSPECTION. |