Permit: T06CM04374

Parcel: 12308007C


Addresses:

3007 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM04374

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/20/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
11/02/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) REMOVED FLOOR SINK NEXT TO HOOD CAPPED OFF BELOW FLOOR OK
10/20/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER, STILL NEED REVISED PLAN FOR WATER PIPE SIZE AND WH AND TYPE LOCATION.
10/19/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO CHANGE SINCE LAST INSPECTION.
YOU ARE USING HANG TUFF PIPE SUPPORTS AS POLE SUPPORTS, RATHER THAN AS HANGERS, THE PIPE IS TO BE SUPPORTED, HANGERS ARE NOT TO BE INSTALLED ON FITTINGS. YOUR WATER PIPING IS UNDERSIZED PER PLAN. THIS BUILDING HAS A 2 1/2" WATER SERVICE. IT IS POSSIBLE TO PROVIDE AN INSTALLATION THAT REPRESENTS THE APPROVED PLANS.
10/11/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
I DON'T BELIEVE THAT ZIP STICKS ARE LISTED TO BE USED AS STAND UP PIPE SUPPORTS. PROVIDE UPC LISTING W/INSTALLATION INSTRUCTIONS OR PROPERLY SUPPORT PIPING AT VENT OFFSET.
COPPER AT SODA LOCATION OK TO COVER.
10/09/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
JOB SITE LOCKED, UNABLE TO INSPECT.
10/06/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CORRECT VENT
SECURE AND ISOLATE COPPER AT SODA
OK TO COVER OTHER AREAS
GAS PRESSURE TEST OK
10/05/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- WH NOT PER PLAN
- WATER PIPING NOT SIZED PER PLAN ALSO REMOVE EXCESS FLUX.
- SECURE DROP EARED ELL AT HB AND INSTALL NONFURROUS PIPE NIPPLE.
- VENT AT HAND SINK IS LESS THAN 10' FROM FORCED AIR INLET -- OFFSET
- CONDENSATE CONNECTION TO VENT ON ROOF SHALL BE PIPED TO APPROVED LOCATION AND INSPECTED BY MECHANICAL INSPECTOR -- REPAIR VENT.
- PRESSURE TEST ON STREAM OF ANSUL VALVE IS OK, NOT TEST UPSTREAM PIPING. CAP ELIMINATED GAS PIPING.

NOTE: EXISTING PLUMBING APPERTENENCES SHALL BE BROUGHT UP TO CURRENT CODE REQUIREMENTS.