Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM04374
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/23/2007 | ELECTRIC - FINAL | Approved | ||
03/22/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EMERGENCY LIGHTING MISSING/NOT PER PLAN AND NEEDS TO COMPLY WITH NEC 700.11E 2. BREAKERS TO BE BRYANT OR WESTINGHOUSE ONLY PER PANEL LABEL -- NEC 110.3 B 3. J-BOX ABOVE PANEL IN CEILING OVERFILLED - NEC 314.16 AND ANY OTHERS 4. PROVIDE A DISCONNECTING MEANS FOR ALL APPLIANCES PER NEC 422.31 5. GFI PROTECTION IS REQUIRED FOR ALL 15 & 20 AMP 120V RECEPTACLES IN KITCHEN - NEC 210.8 B3 6. PROVIDE INSTALLATION SHEET ON DIMMERS THAT ARE GANGED SO I CAN CHECK FOR PROPER WATTAGE DERATION -- NEC 110.3B 7. PANEL DIRECTORY'S TO BE CORRECT AND LEGIBLY MARKED (NEAT) NEC 408.4 8. PROVIDE ROOF ACCESS |
|
03/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : 1. MISSING RECEPT PLATE IN DINING ROOM 2. INSTALL BOX EXTENSION ON RECEPT IN WOOD WALLS DINING ROOM 3. INSTALL FAN COVER WOMENS RESTROOM 4. OPEN JUNCTION BOX IN CEILING HOUSE PANELS 5. INSTALL WESTINGHOUSE OR BRYANT BREAKERS IN PANELS OR PROVIDE LISTING. 6. INSTALL ONLY CTL TAPE TWIN BREAKERS IN PANEL (NON-CTL TYPE BREAKERS ARE INSTALLED) 7. IDENTIFY NEUTRAL AT PANEL A FOR PANEL B 8. EXIT SIGN AT BACK DOOR NOT OPERATING 9. NO ELECTRICAL DRAWINGS ON SITE 10. NEED ACCURATE PANEL SCHEDULES 11. UNABLE TO CHECK EMERGENCY LIGHTING. NEED SOMEONE ON SITE TO TEST. 12. THIS MAY NOT BE A COMPLETE LIST 13. HAVE THIS LIST ON SITE FOR REINSPECTION. |