Permit: T06CM04374

Parcel: 12308007C


Addresses:

3007 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04374

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/23/2007 ELECTRIC - FINAL Approved
03/22/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EMERGENCY LIGHTING MISSING/NOT PER PLAN AND NEEDS TO COMPLY WITH NEC 700.11E
2. BREAKERS TO BE BRYANT OR WESTINGHOUSE ONLY PER PANEL LABEL -- NEC 110.3 B
3. J-BOX ABOVE PANEL IN CEILING OVERFILLED - NEC 314.16
AND ANY OTHERS
4. PROVIDE A DISCONNECTING MEANS FOR ALL APPLIANCES PER NEC 422.31
5. GFI PROTECTION IS REQUIRED FOR ALL 15 & 20 AMP 120V RECEPTACLES IN KITCHEN - NEC 210.8 B3
6. PROVIDE INSTALLATION SHEET ON DIMMERS THAT ARE GANGED SO I CAN CHECK FOR PROPER WATTAGE DERATION -- NEC 110.3B
7. PANEL DIRECTORY'S TO BE CORRECT AND LEGIBLY MARKED
(NEAT) NEC 408.4
8. PROVIDE ROOF ACCESS
03/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
1. MISSING RECEPT PLATE IN DINING ROOM
2. INSTALL BOX EXTENSION ON RECEPT IN WOOD WALLS DINING ROOM
3. INSTALL FAN COVER WOMENS RESTROOM
4. OPEN JUNCTION BOX IN CEILING HOUSE PANELS
5. INSTALL WESTINGHOUSE OR BRYANT BREAKERS IN PANELS OR PROVIDE LISTING.
6. INSTALL ONLY CTL TAPE TWIN BREAKERS IN PANEL (NON-CTL TYPE BREAKERS ARE INSTALLED)
7. IDENTIFY NEUTRAL AT PANEL A FOR PANEL B
8. EXIT SIGN AT BACK DOOR NOT OPERATING
9. NO ELECTRICAL DRAWINGS ON SITE
10. NEED ACCURATE PANEL SCHEDULES
11. UNABLE TO CHECK EMERGENCY LIGHTING. NEED SOMEONE ON SITE TO TEST.
12. THIS MAY NOT BE A COMPLETE LIST
13. HAVE THIS LIST ON SITE FOR REINSPECTION.