Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 08/10/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK CEILING TILES RETAIL AREA |
|
| 08/08/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 08/07/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. HAVE OVERFILLED J-BOXES -- NEC 314.16 2. HAVE TO MANY CONDUCTORS UNDER WIRE NUTS NEC 110.3B 3. DEMO UNUSED RACEWAYS & WIRING 4. FINISH WIRING ABOVE CEILING 5. SUPPORT FIXTURES PER NEC 300.11 PARTIAL INSPECTION/NOT READY GO THROUGH WORK |