Permit: T06CM04366

Parcel: 11615194B

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
03/06/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
OK TO FINISH SHEET ROCK
02/21/2007 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE MIN. 1" CLEARANCE FROM COMBUSTIBLES AROUND WATER HEATER VENT.
2. RAISE COMBUSTION VENT TO WITHIN 12" OF CEILING & SECURE IN PLACE.
02/12/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK FOR SHEETROCK EXCEPT WATER HEATER ROOM