Permit: T06CM04350

Parcel: 111080610

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM04350

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/24/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
05/12/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CORRECTIONS MADE OK
OK TO COVER ALL AREAS
NEED TO SEE CLOSET FLANGES
05/07/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. UNITS #6 & #7 OK TO COVER WALLS
NEED TO SEE FLANGES
GAS PRESSURE TEST OK
GAS PRESSRE TEST ON #5 OK
2. UNIT #5 THE KITCHEN SINK AND LAVATORY WASTE PIPING DOES NOT MEET MINIMUM STD. FOR DWV INSTALLATION
REQUIRE DRAINAGE FITTINGS
REQUIRE VENT
TRAP AMRS TO BE WITHIN DISTANCE ALLOWED
OFFSETS NOT PERMITTED ON TRAP ARMS
1/4" PITCH ON ALL DRAINAGE PIPE