Permit: T06CM04350

Parcel: 111080610

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04350

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/05/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK UNITS 5, 6, 7

WAITING ON LETTER FROM CONTRACTOR VERIFYING CONDITION OF SERVICE EQUIPMENT
08/04/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
07/28/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
#7:
1. PROTECT BULB IN CLOSET
2. A BOX IS NEEDED AT BATH GFCI
3. BOXES WITH NEW OUTLETS NEED APPROVED EXTENDER RINGS IF MORE THAN 1/4"
4. NO COOLING AT THIS TIME - NEEDED FOR MOVING HOUSING
5. COOLER CORD TO BE MAX 6'

MAIN SERVICE:
1. MAINS TO BE 80 AMPS BASED ON DERATING
2. METER SECTION SHOWS SIGNS OF ARCING TO ENCLOSURE
PLEASE CHECK
07/23/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
ROOF:
1. BOX SIZE TOO SMALL FOR ANGLE POLL
2. VERIFY DERATING OF CONDUCTORS FOR FILL & HEAT
310.15 AND 310.16
3. LABEL MIDWEST BOX
4. NEED FUSES
5. TIGHTEN LOOSE FITTING
6. SEAL ENTRANCE TOP OF SERVICE

THIS IS UNIT #5 ONLY


1. GROUND BROKEN AT RECEPTACLE
2. A CONNECTOR IS NEEDED AT HOOD
3. LABEL PANEL DIRECTORY AS PER 408.4 NO ABBREVIATIONS
ALSO, UNIT ON OUTSIDE OF COVER
4. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL
WITH A NON-COMBUSTIBLE