Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/05/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK UNITS 5, 6, 7 WAITING ON LETTER FROM CONTRACTOR VERIFYING CONDITION OF SERVICE EQUIPMENT |
|
| 08/04/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/28/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* #7: 1. PROTECT BULB IN CLOSET 2. A BOX IS NEEDED AT BATH GFCI 3. BOXES WITH NEW OUTLETS NEED APPROVED EXTENDER RINGS IF MORE THAN 1/4" 4. NO COOLING AT THIS TIME - NEEDED FOR MOVING HOUSING 5. COOLER CORD TO BE MAX 6' MAIN SERVICE: 1. MAINS TO BE 80 AMPS BASED ON DERATING 2. METER SECTION SHOWS SIGNS OF ARCING TO ENCLOSURE PLEASE CHECK |
|
| 07/23/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* ROOF: 1. BOX SIZE TOO SMALL FOR ANGLE POLL 2. VERIFY DERATING OF CONDUCTORS FOR FILL & HEAT 310.15 AND 310.16 3. LABEL MIDWEST BOX 4. NEED FUSES 5. TIGHTEN LOOSE FITTING 6. SEAL ENTRANCE TOP OF SERVICE THIS IS UNIT #5 ONLY 1. GROUND BROKEN AT RECEPTACLE 2. A CONNECTOR IS NEEDED AT HOOD 3. LABEL PANEL DIRECTORY AS PER 408.4 NO ABBREVIATIONS ALSO, UNIT ON OUTSIDE OF COVER 4. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE |