Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM04350
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/05/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/23/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS & CEILINGS |
|
05/09/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UNIT #6 1. ENTRY SWITCHES TO BE ON RIGHT SIDE OF DOOR 2. NEED HALLWAY RECEPTACLE 3. NEED REAR EXTERIOR SWITCHED LIGHT 4. NEED RECEPTACLE BEDROOM ENTRY WALL UNIT #7 1. LOOSEN KITCHEN FIXTURE TO THE POINT OF GOOD INSULATION UNIT #5 1. NEED BACK PORCH LIGHT OK COVER ALL UNITS AFTER CORRECTIONS REMOVE ALL OLD RECEPTACLES 2 WIRE RECEPTACLES REQUIRED WHERE NO GROUND EXISTS |