Permit: T06CM04348

Parcel: 10703141E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/14/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/13/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
- HAVE CONTRACTOR AND PLANS ON SITE
- PROVIDE ACCESS TO ROOF AND ALL EQUIPMENT FOR INSPECTION.
- LEAVE A MESSAGE WHEN YOU RESCHEDULE IF YOU NEED AN ADVANCE CALL.
10/05/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
SERVICE INSPECTION ONLY
TRANSFORMERS TO BE PROPERLY GROUNDED NEC 250.30
10/04/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
10/02/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
COMPLETE ALL CORRECTIONS BEFORE INSPECTION.
09/25/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PARTIAL INSPECTION ONLY BASED ON 2002 NEC
1. RACEWAYS BETWEEN TERMINATION CAN AND CT CAN NEED TO BE BONDED -- NEC 250.92
2. SAME RACEWAYS NEED TO BE STRAPPED BETWEEN CANS -- NEC 344.30
3. BONDING CONDUCTOR TO CT ENCLOSURE IS UNDERSIZED --
NEC 250.102 (D)
4. NEUTRAL CONDUCTOR TO BE ROUTED TO SERVICE DISCONNECT -- NEC 250.24 (B)
5. BOND RACEWAYS BETWEEN CT CAN AND DISCONNECT -- NEC 250.92
6. STRAP SAME RACEWAYS WITHIN 3' OF CT CAN ENTRY --
NEC 344.30
7. SERVICE DISCONNECT NEEDS NEUTRAL KIT INSTALLED -- READ COVER INSTRUCTIONS -- NEC 110.3(B), NEC 230.66 AND IDENTIFY AS "SERVICE DISCONNECT" -- NEC 230.70(C)
8. SERVICE DISCONNECT NOT PROPERLY BONDED --
NEC 250.24 (B) OR 250.102 (D)
9. ALL EQUIPMENT TO BE SECURELY MOUNTED -- NEC 110.13
10. TIGHTEN ALL RACEWAY FITTINGS -- NEC 110, 300
11. SECURE TRANSFORMER IN PLACE -- NEC 110.13
12. TRANSFORMERS NOT GROUNDED PER CODE -- NEC 250.30 (READ ALL)
13. STRAP FLEX BETWEEN TRANSFORMER AND DISCONNECT - NEC 350.30
14. IDENTIFY ALL DISCONNECTS -- NEC 110.22
15. DO NOT INSTALL DIFFERENT SIZE OR TYPE CONDUCTORS UNDER SAME LUG. -- NEC 110.14
16. REMOVE PAINT UNDER LUGS AND TIGHTEN ALL CONNECTIONS -- NEC 110
17. INTERIOR TRANSFORMER TO BE PROPERLY GROUNDED -- NEC 250.30, SECURED TO FLOOR -- NEC 110.13 IDENTIFY DISCONNECT.