Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* - HAVE CONTRACTOR AND PLANS ON SITE - PROVIDE ACCESS TO ROOF AND ALL EQUIPMENT FOR INSPECTION. - LEAVE A MESSAGE WHEN YOU RESCHEDULE IF YOU NEED AN ADVANCE CALL. |
|
| 10/05/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* SERVICE INSPECTION ONLY TRANSFORMERS TO BE PROPERLY GROUNDED NEC 250.30 |
|
| 10/04/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 10/02/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* COMPLETE ALL CORRECTIONS BEFORE INSPECTION. |
|
| 09/25/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* PARTIAL INSPECTION ONLY BASED ON 2002 NEC 1. RACEWAYS BETWEEN TERMINATION CAN AND CT CAN NEED TO BE BONDED -- NEC 250.92 2. SAME RACEWAYS NEED TO BE STRAPPED BETWEEN CANS -- NEC 344.30 3. BONDING CONDUCTOR TO CT ENCLOSURE IS UNDERSIZED -- NEC 250.102 (D) 4. NEUTRAL CONDUCTOR TO BE ROUTED TO SERVICE DISCONNECT -- NEC 250.24 (B) 5. BOND RACEWAYS BETWEEN CT CAN AND DISCONNECT -- NEC 250.92 6. STRAP SAME RACEWAYS WITHIN 3' OF CT CAN ENTRY -- NEC 344.30 7. SERVICE DISCONNECT NEEDS NEUTRAL KIT INSTALLED -- READ COVER INSTRUCTIONS -- NEC 110.3(B), NEC 230.66 AND IDENTIFY AS "SERVICE DISCONNECT" -- NEC 230.70(C) 8. SERVICE DISCONNECT NOT PROPERLY BONDED -- NEC 250.24 (B) OR 250.102 (D) 9. ALL EQUIPMENT TO BE SECURELY MOUNTED -- NEC 110.13 10. TIGHTEN ALL RACEWAY FITTINGS -- NEC 110, 300 11. SECURE TRANSFORMER IN PLACE -- NEC 110.13 12. TRANSFORMERS NOT GROUNDED PER CODE -- NEC 250.30 (READ ALL) 13. STRAP FLEX BETWEEN TRANSFORMER AND DISCONNECT - NEC 350.30 14. IDENTIFY ALL DISCONNECTS -- NEC 110.22 15. DO NOT INSTALL DIFFERENT SIZE OR TYPE CONDUCTORS UNDER SAME LUG. -- NEC 110.14 16. REMOVE PAINT UNDER LUGS AND TIGHTEN ALL CONNECTIONS -- NEC 110 17. INTERIOR TRANSFORMER TO BE PROPERLY GROUNDED -- NEC 250.30, SECURED TO FLOOR -- NEC 110.13 IDENTIFY DISCONNECT. |